FAQ# DRV-5JW398 Published: 07/13/2004

Question:A Siemens Apogee FLN option board is installed on GPD506 bypass drive so a run command can be initiated through network communications. After a safety circuit fault has been reset, the drive will not run again even though it has been commanded to. Why is this happening?
Answer:This problem will occur while using Siemens Application 2712, if specific criteria is not met. The solution includes adding a wire within the bypass cabinet, and correctly setting up the Siemens command points for initiating a network run command.

Here is a detailed description of the solution:

The GPD506 bypass drive has a terminal block labeled TB1 which contains terminals 3 & 4 for connecting run command wires. Since Serial communications is being used for the run command, there needs to be a jumper installed between terminals 3 & 4 to allow the K5 relay inside the cabinet to be energized. The safety circuit is located before this jumper so if it opens, the run command will be broken and the drive will stop.

The Siemens network will control when the drive can restart again. There are several Siemens command points that have to be set correctly for this to occur, and they are shown below. This information is found in the GPD506/P5 Apogee - FLN Technical Manual (TM4029).
Download the TM4029 manual.








Product Information:

Product Group:Inverters/Drives
Product:Network Comms - Landis FLN
Applications:
Category:Start up; Troubleshooting

Other Information:

Link to related files:

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF FAQ INFORMATION!
Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. FAQ content and illustrations are provided as technical advice to augment the information in manual, not superceed it. It is not possible to give detailed instructions for all types of installation or support activities. The information described in the FAQs are subject to change without notice to improve the product or FAQ. Yaskawa assumes no responsibility for errors or omissions or damages resulting from the use of the information contained in any FAQ. All warnings, cautions and product instruction for product use must be followed. Installation, operation and maintenance should be carried out by qualified personnel. Failure to observe these and other precautions highlighted in the product manuals will expose the user to high voltages resulting in, serious injury or death. Qualified personnel are defined as individuals who are familiar with the installation, starting, operation and maintenance of Yaskawa products of the type described and have proper qualifications to perform the work.