A1000 Drive
Models & Ratings
200-240V, 3-Phase: Protected Chassis/NEMA 1 | Flange | 1-Phase: Standard
380-480V, 3-Phase: Protected Chassis/NEMA 1 | Flange | 12-Pulse | 1-Phase: Standard/NEMA 1
500-600V, 3-Phase: Protected Chassis/NEMA 1 | Flange | 1-Phase: Standard
200-240V, 3-Phase, Protected Chassis/NEMA 1
Drive Model Number Standard | Normal Duty (ND)1 | Heavy Duty (HD)1 | Standard Enclosure | ||
---|---|---|---|---|---|
Rated Output Current (Amps) | Nominal HP2 | Rated Output Current (Amps) | Nominal HP2 | ||
CIMR-AU2A0004FAA | 3.5 | 3/4 | 3.2 | 3/4 | NEMA 1 |
CIMR-AU2A0006FAA | 6 | 1 | 5 | 1 | |
CIMR-AU2A0008FAA | 8 | 2 | 6.9 | 2 | |
CIMR-AU2A0010FAA | 9.6 | 2 | 8 | 2 | NEMA 1 |
CIMR-AU2A0012FAA | 12 | 3 | 11 | 3 | |
CIMR-AU2A0018FAA | 17.5 | 5 | 14 | 3 | |
CIMR-AU2A0021FAA | 21 | 7.5 | 17.5 | 5 | NEMA 1 |
CIMR-AU2A0030FAA | 30 | 10 | 25 | 7.5 | |
CIMR-AU2A0040FAA | 40 | 15 | 33 | 10 | |
CIMR-AU2A0056FAA | 56 | 20 | 47 | 15 | NEMA 1 |
CIMR-AU2A0069FAA | 69 | 25 | 60 | 20 | |
CIMR-AU2A0081FAA | 81 | 30 | 75 | 25 | |
CIMR-AU2A0110FAA | 110 | 40 | 85 | 30 | NEMA 1 |
CIMR-AU2A0138FAA | 138 | 50 | 115 | 40 | |
CIMR-AU2A0169FAA | 169 | 60 | 145 | 50 | NEMA 1 |
CIMR-AU2A0211FAA | 211 | 75 | 180 | 60 | |
CIMR-AU2A0250AAA | 250 | 100 | 215 | 75 | Protected Chassis |
CIMR-AU2A0312AAA | 312 | 125 | 283 | 100 | |
CIMR-AU2A0360AAA | 360 | 150 | 346 | 125 | Protected Chassis |
CIMR-AU2A0415AAA | 415 | 175 | 415 | 150 |
- Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
- Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors. Also, listed power ratings assumes three-phase input. For single-phase input applications, consult Manual Supplement TOEPYEASUP03 for proper sizing.
200-240V, 3-Phase, Flange
Drive Model Number Flange1 | Normal Duty (ND)2 | Heavy Duty (HD)2 | Enclosure1 | ||
---|---|---|---|---|---|
Rated Output Current (Amps) | Nominal HP3 | Rated Output Current (Amps) | Nominal HP3 | ||
CIMR-AU2A0004UAA | 3.5 | 3/4 | 3.2 | 3/4 | Flange |
CIMR-AU2A0006UAA | 6 | 1 | 5 | 1 | |
CIMR-AU2A0008UAA | 8 | 2 | 6.9 | 2 | |
CIMR-AU2A0010UAA | 9.6 | 3 | 8 | 2 | Flange |
CIMR-AU2A0012UAA | 12 | 3 | 11 | 3 | |
CIMR-AU2A0018UAA | 17.5 | 5 | 14 | 3 | |
CIMR-AU2A0021UAA | 21 | 7.5 | 17.5 | 5 | Flange |
CIMR-AU2A0030UAA | 30 | 10 | 25 | 7.5 | |
CIMR-AU2A0040UAA | 40 | 15 | 33 | 10 | |
CIMR-AU2A0056UAA | 56 | 20 | 47 | 15 | Flange |
CIMR-AU2A0069UAA | 69 | 25 | 60 | 20 | |
CIMR-AU2A0081UAA | 81 | 30 | 75 | 25 | |
CIMR-AU2A0110UAA | 110 | 40 | 85 | 30 | Flange |
CIMR-AU2A0138UAA | 138 | 50 | 115 | 40 | |
CIMR-AU2A0169UAA | 169 | 60 | 145 | 50 | |
CIMR-AU2A0211UAA | 211 | 75 | 180 | 60 | Flange |
CIMR-AU2A0250UAA | 250 | 100 | 215 | 75 | |
CIMR-AU2A0312UAA | 312 | 125 | 283 | 100 | |
CIMR-AU2A0360UAA | 360 | 150 | 346 | 125 | Flange |
CIMR-AU2A0415UAA | 415 | 175 | 415 | 150 |
- Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
- Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
- Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430. 150 Full-Load Current, Three-Phase Alternating Current Motors
240V, Single-Phase Input, (208-230V Three-Phase Output)
Drive Model Number 1, 2, 3 | Single Phase Input - Sizing Method A (A) (continuous full power) | Single Phase Input - Sizing Method B (B) (86% max power of connected motor size) | ||||
---|---|---|---|---|---|---|
Without Additional Reactor | With Additional Reactor | |||||
Motor Amps | Motor Size (HP) | Motor Amps | Motor Size (HP) | Motor Amps | Motor Size (HP) | |
CIMR-AU2A0004FAA | 1.7 | 1/3 | 2.4 | 1/2 | 2.4 | 1/2 |
CIMR-AU2A0006FAA | 3.5 | 3/4 | 3.5 | 3/4 | 4.6 | 1 |
CIMR-AU2A0008FAA | 4.6 | 1 | 4.6 | 1 | 4.6 | 1 |
CIMR-AU2A0010FAA | 4.6 | 1 | 4.6 | 1 | 6.6 | 1.5 |
CIMR-AU2A0012FAA | 6.6 | 1.5 | 7.5 | 2 | 7.5 | 2 |
CIMR-AU2A0018FAA | 7.5 | 2 | 10.6 | 3 | 10.6 | 3 |
CIMR-AU2A0021FAA | 7.5 | 2 | 10.6 | 3 | 10.6 | 3 |
CIMR-AU2A0030FAA | 10.6 | 3 | 10.6 | 3 | 17.0 | 5 |
CIMR-AU2A0040FAA | 10.6 | 3 | 17 | 5 | 17.0 | 5 |
CIMR-AU2A0056FAA | 17 | 5 | 24 | 7.5 | 24.0 | 7.5 |
CIMR-AU2A0069FAA | 24 | 7.5 | 31 | 10 | 31.0 | 10 |
CIMR-AU2A0081FAA | 31 | 10 | 46 | 15 | 46 | 15 |
CIMR-AU2A0110FAA | 31 | 10 | 31 | 10 | 46 | 15 |
CIMR-AU2A0138FAA | 46 | 15 | 46 | 15 | 59 | 20 |
CIMR-AU2A0169FAA | 59 | 20 | 59 | 20 | 75 | 25 |
CIMR-AU2A0211FAA | 75 | 25 | 75 | 25 | 88 | 30 |
CIMR-AU2A0250AAA | 88 | 30 | 88 | 30 | 114 | 40 |
CIMR-AU2A0312AAA | 114 | 40 | 114 | 40 | 143 | 50 |
CIMR-AU2A0360AAA | 143 | 50 | 143 | 50 | 169 | 60 |
CIMR-AU2A0415AAA | 169 | 60 | 169 | 60 | 211 | 75 |
- Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A0081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
- Only models ending in FAA (CIMR-AU2A0211FAA and smaller) come standard with NEMA 1 End Cap Kits. Separately sold kits are available for larger models.
- For Flange Drives, use the sizing method above to determine proper drive size. Use selected model numbers with "UAA" suffix instead of "FAA" or "AAA" suffix.
- Use single phase input sizing method A for applications requiring more than 86% motor power. When sizing with additional reactor, consult factory. Caution: Adding more impedance than specified will degrade performance.
- Use single phase input sizing method B for applications requiring a maximum of 86% motor power.
380-480V, 3-Phase, Protected Chassis/NEMA 1
Drive Model Number Standard | Normal Duty (ND)1 | Heavy Duty (HD)1 | Standard Enclosure | ||
---|---|---|---|---|---|
Rated Output Current (Amps) | Nominal HP2 | Rated Output Current (Amps) | Nominal HP2 | ||
CIMR-AU4A0002FAA | 2.1 | 3/4 & 1 | 1.8 | 3/4 | NEMA 1 |
CIMR-AU4A0004FAA | 4.1 | 2 | 3.4 | 1 & 2 | |
CIMR-AU4A0005FAA | 5.4 | 3 | 4.8 | 3 | |
CIMR-AU4A0007FAA | 6.9 | 4 | 5.5 | 3 | NEMA 1 |
CIMR-AU4A0009FAA | 8.8 | 5 | 7.2 | 4 | |
CIMR-AU4A0011FAA | 11.1 | 7.5 | 9.2 | 5 | |
CIMR-AU4A0018FAA | 17.5 | 10 | 14.8 | 7.5 & 10 | NEMA 1 |
CIMR-AU4A0023FAA | 23 | 15 | 18 | 10 | |
CIMR-AU4A0031FAA | 31 | 20 | 24 | 15 | |
CIMR-AU4A0038FAA | 38 | 25 | 31 | 20 | NEMA 1 |
CIMR-AU4A0044FAA | 44 | 30 | 39 | 25 & 30 | |
CIMR-AU4A0058FAA | 58 | 40 | 45 | 30 | |
CIMR-AU4A0072FAA | 72 | 50 | 60 | 40 | NEMA 1 |
CIMR-AU4A0088FAA | 88 | 60 | 75 | 50 & 60 | |
CIMR-AU4A0103FAA | 103 | 75 | 91 | 60 | |
CIMR-AU4A0139FAA | 139 | 100 | 112 | 75 | NEMA 1 |
CIMR-AU4A0165FAA | 165 | 125 | 150 | 100 | |
CIMR-AU4A0208AAA | 208 | 150 | 180 | 125 & 150 | Protected Chassis |
CIMR-AU4A0250AAA | 250 | 200 | 216 | 150 | |
CIMR-AU4A0296AAA | 296 | 250 | 260 | 200 | |
CIMR-AU4A0362AAA | 362 | 300 | 304 | 250 | Protected Chassis |
CIMR-AU4A0414AAA | 414 | 350 | 370 | 300 | |
CIMR-AU4A0515AAA | 515 | 400 | 450 | 350 | Protected Chassis |
CIMR-AU4A0675AAA | 675 | 500 | 605 | 400-500 | |
CIMR-AU4A0930AAA | 930 | 700-800 | 810 | 600-700 | Protected Chassis |
CIMR-AU4A1200AAA | 1200 | 900-1000 | 1090 | 800-900 |
- Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
- Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors. Also, listed power ratings assumes three-phase input. For single-phase input applications, consult Manual Supplement TOEPYEASUP03 for proper sizing.
380-480V, 3-Phase, Flange
Drive Model Number Flange1 | Normal Duty (ND)2 | Heavy Duty (HD)2 | Enclosure1 | ||
---|---|---|---|---|---|
Rated Output Current (Amps) | Nominal HP3 | Rated Output Current (Amps) | Nominal HP3 | ||
CIMR-AU4A0002UAA | 2.1 | 1 | 1.8 | 3/4 | Flange |
CIMR-AU4A0004UAA | 4.1 | 2 | 3.4 | 1 & 2 | |
CIMR-AU4A0005UAA | 5.4 | 3 | 4.8 | 3 | |
CIMR-AU4A0007UAA | 6.9 | 4 | 5.5 | 3 | Flange |
CIMR-AU4A0009UAA | 8.8 | 5 | 7.2 | 5 | |
CIMR-AU4A0011UAA | 11.1 | 7.5 | 9.2 | 5 | |
CIMR-AU4A0018UAA | 17.5 | 10 | 14.8 | 7.5 & 10 | Flange |
CIMR-AU4A0023UAA | 23 | 15 | 18 | 10 | |
CIMR-AU4A0031UAA | 31 | 20 | 24 | 15 | |
CIMR-AU4A0038UAA | 38 | 25 | 31 | 20 | Flange |
CIMR-AU4A0044UAA | 44 | 30 | 39 | 25 & 30 | |
CIMR-AU4A0058UAA | 58 | 40 | 45 | 30 | |
CIMR-AU4A0072UAA | 72 | 50 | 60 | 40 | Flange |
CIMR-AU4A0088UAA | 88 | 60 | 75 | 50 & 60 | |
CIMR-AU4A0103UAA | 103 | 75 | 91 | 60 | |
CIMR-AU4A0139UAA | 139 | 100 | 112 | 75 | Flange |
CIMR-AU4A0165UAA | 165 | 125 | 150 | 100 | |
CIMR-AU4A0208UAA | 208 | 150 | 180 | 125 & 150 | Flange |
CIMR-AU4A0250UAA | 250 | 200 | 216 | 150 | |
CIMR-AU4A0296UAA | 296 | 250 | 260 | 200 | |
CIMR-AU4A0362UAA | 362 | 300 | 304 | 250 | Flange |
CIMR-AU4A0414UAA | 414 | 350 | 370 | 300 | |
CIMR-AU4A0515UAA | 515 | 400 | 450 | 350 | Flange |
CIMR-AU4A0675UAA | 675 | 500 | 605 | 400-500 | |
CIMR-AU4A0930UAA4 | 930 | 700-800 | 810 | 600-700 | Flange |
CIMR-AU4A1200UAA4 | 1200 | 900-1000 | 1090 | 800-900 |
- Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
- Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
- Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430. 150 Full-Load Current, Three-Phase Alternating Current Motors
- Models CIMR-AU4A0930UAA and CIMR-AU4A1200UAA must be used with semiconductor input fuses and must be fed by a power source that has ground fault protection. A supplementary ground fault protection device can be added between the drive and the power source to address this requirement.
380-480V, 3-Phase,12-Pulse
Drive Model Number 12-Pulse Flange1 | Normal Duty (ND)2 | Heavy Duty (HD)2 | Enclosure1 | ||
---|---|---|---|---|---|
Rated Output Current (Amps) | Nominal HP3 | Rated Output Current (Amps) | Nominal HP3 | ||
CIMR-AU4T0058UAA | 58 | 40 | 45 | 30 | Flange |
CIMR-AU4T0072UAA | 72 | 50 | 60 | 40 | |
CIMR-AU4T0088UAA | 88 | 60 | 75 | 50 & 60 | Flange |
CIMR-AU4T0103UAA | 103 | 75 | 91 | 60 | |
CIMR-AU4T0139UAA | 139 | 100 | 112 | 75 | Flange |
CIMR-AU4T0165UAA | 165 | 125 | 150 | 100 | |
CIMR-AU4T0208UAA | 208 | 150 | 180 | 125 & 150 | Flange |
CIMR-AU4T0250UAA | 250 | 200 | 216 | 150 | |
CIMR-AU4T0296UAA | 296 | 250 | 260 | 200 | |
CIMR-AU4T0362UAA | 362 | 300 | 304 | 250 | Flange |
CIMR-AU4T0414UAA | 414 | 350 | 370 | 300 | |
CIMR-AU4T0515UAA | 515 | 400 | 450 | 350 | Flange |
CIMR-AU4T0675UAA | 675 | 500-600 | 605 | 400-500 | |
See note 4 | 930 | 700-800 | 810 | 600-700 | Fnlage |
See note 4 | 1200 | 900-1000 | 1090 | 800-900 |
- Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external. Flange parts can be removed if conventional mounting is desired.
- Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds.
- Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors.
- Models CIMR-AU4A0930xxx and CIMR-AU4A1200xxx are user configurable for either 6-Pulse (3-Phase) or 12-Pulse (6-Phase) input. See Standard 480V for model numbers.>
480V, Single-Phase Input, (460V Three-Phase Output)
Drive Model Number 1, 2, 3 | Drive Model Number (NEMA 1 Compatible) | Single Phase Input - Sizing Method A (A) (continuous full power) | Single Phase Input - Sizing Method B (B) (86% max power of connected motor size) | ||||
---|---|---|---|---|---|---|---|
Without Additional Reactor | With Additional Reactor | ||||||
Motor Amps | Motor Size (HP) | Motor Amps | Motor Size (HP) | Motor Amps | Motor Size (HP) | ||
CIMR-AU4A0002FAA | 0.8 | 1/3 | 1.1 | 1/2 | 0.8 | 1/3 | |
CIMR-AU4A0004FAA | 1.6 | 3/4 | 2.1 | 1 | 2.1 | 1 | |
CIMR-AU4A0005FAA | 2.1 | 1 | 3.0 | 1.5 | 3.0 | 1.5 | |
CIMR-AU4A0007FAA | 3.0 | 1.5 | 3.4 | 2 | 3.4 | 2 | |
CIMR-AU4A0009FAA | 3.4 | 2 | 4.8 | 3 | 4.8 | 3 | |
CIMR-AU4A0011FAA | 3.4 | 2 | 4.8 | 3 | 4.8 | 3 | |
CIMR-AU4A0018FAA | 4.8 | 3 | 4.8 | 3 | 7.6 | 5 | |
CIMR-AU4A0023FAA | 4.8 | 3 | 7.6 | 5 | 7.6 | 5 | |
CIMR-AU4A0031FAA | 11 | 7.5 | 11 | 7.5 | 14.0 | 10 | |
CIMR-AU4A0038FAA | 11 | 7.5 | 14 | 10 | 14.0 | 10 | |
CIMR-AU4A0044FAA | 14 | 10 | 14 | 10 | 21.0 | 15 | |
CIMR-AU4A0058FAA | 21 | 15 | 21 | 15 | 27.0 | 20 | |
CIMR-AU4A0072FAA | 27 | 20 | 27 | 20 | 34.0 | 25 | |
CIMR-AU4A0088FAA | 27 | 20 | 27 | 20 | 34.0 | 25 | |
CIMR-AU4A0103FAA | 27 | 20 | 27 | 20 | 34.0 | 25 | |
CIMR-AU4A0139FAA | 52 | 40 | 52 | 40 | 65.0 | 50 | |
CIMR-AU4A0165FAA | 52 | 40 | 52 | 40 | 65.0 | 50 | |
CIMR-AU4A0208AAA | 65 | 50 | 65 | 50 | 77.0 | 60 | |
CIMR-AU4A0250AAA | 77 | 60 | 77 | 60 | 96 | 75 | |
CIMR-AU4A0296AAA | 96 | 75 | 96 | 75 | 124 | 100 | |
CIMR-AU4A0362AAA | 124 | 100 | 124 | 100 | 156 | 125 | |
CIMR-AU4A0414AAA | CIMR-UUX000679 | 156 | 125 | 156 | 125 | 180 | 150 |
CIMR-AU4A0515AAA | CIMR-UUX000680 | 156 | 125 | 156 | 125 | 180 | 150 |
CIMR-AU4A0675AAA | CIMR-UUX000681 | 180 | 150 | 180 | 150 | 240 | 200 |
- Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A0081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
- Only models ending in FAA (CIMR-AU2A0211FAA and smaller) come standard with NEMA 1 End Cap Kits. Separately sold kits are available for larger models.
- For Flange Drives, use the sizing method above to determine proper drive size. Use selected model numbers with "UAA" suffix instead of "FAA" or "AAA" suffix.
- Use single phase input sizing method A for applications requiring more than 86% motor power. When sizing with additional reactor, consult factory. Caution: Adding more impedance than specified will degrade performance.
- Use single phase input sizing method B for applications requiring a maximum of 86% motor power.
500-600V, 3-Phase, Protected Chassis/NEMA 1
Drive Model Number Standard | Normal Duty (ND)1 | Heavy Duty (HD)1 | Standard Enclosure | ||
---|---|---|---|---|---|
Rated Output Current (Amps) | Nominal HP2 | Rated Output Current (Amps) | Nominal HP2 | ||
CIMR-AU5A0003FAA | 2.7 | 1 & 2 | 1.7 | 1 | NEMA 1 |
CIMR-AU5A0004FAA | 3.9 | 3 | 3.5 | 2 | |
CIMR-AU5A0006FAA | 6.1 | 5 | 4.1 | 3 | |
CIMR-AU5A0009FAA | 9 | 7.5 | 6.3 | 5 | NEMA 1 |
CIMR-AU5A0011FAA | 11 | 10 | 9.8 | 7.5 | |
CIMR-AU5A0017FAA | 17.5 | 15 | 12.5 | 10 | |
CIMR-AU5A0022FAA | 22 | 20 | 17 | 15 | NEMA 1 |
CIMR-AU5A0027FAA | 27 | 25 | 22 | 20 | |
CIMR-AU5A0032FAA | 32 | 30 | 27 | 25 | |
CIMR-AU5A0041FAA | 41 | 40 | 32 | 30 | NEMA 1 |
CIMR-AU5A0052FAA | 52 | 50 | 41 | 40 | |
CIMR-AU5A0062FAA | 62 | 60 | 52 | 50 | |
CIMR-AU5A0077FAA | 77 | 75 | 62 | 60 | NEMA 1 |
CIMR-AU5A0099FAA | 99 | 100 | 77 | 75 | |
CIMR-AU5A0125AAA | 125 | 125 | 99 | 100 | Protected Chassis |
CIMR-AU5A0145AAA | 145 | 150 | 130 | 125 | |
CIMR-AU5A0192AAA | 192 | 200 | 172 | 150 | Protected Chassis |
CIMR-AU5A0242AAA | 242 | 250 | 200 | 200 |
- Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
- Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors. Also, listed power ratings assumes three-phase input. For single-phase input applications, consult Manual Supplement TOEPYEASUP03 for proper sizing.
500-600V, 3-Phase, Flange
Drive Model Number Flange1 | Normal Duty (ND)2 | Heavy Duty (HD)2 | Enclosure1 | ||
---|---|---|---|---|---|
Rated Output Current (Amps) | Nominal HP3 | Rated Output Current (Amps) | Nominal HP3 | ||
CIMR-AU5A0003UAA | 2.7 | 1 & 2 | 1.7 | 1 | Flange |
CIMR-AU5A0004UAA | 3.9 | 3 | 3.5 | 2 | |
CIMR-AU5A0006UAA | 6.1 | 5 | 4.1 | 3 | |
CIMR-AU5A0009UAA | 9 | 7.5 | 6.3 | 5 | Flange |
CIMR-AU5A0011UAA | 11 | 10 | 9.8 | 7.5 | |
CIMR-AU5A0017UAA | 17.5 | 15 | 12.5 | 10 | |
CIMR-AU5A0022UAA | 22 | 20 | 17 | 15 | Flange |
CIMR-AU5A0027UAA | 27 | 25 | 22 | 20 | |
CIMR-AU5A0032UAA | 32 | 30 | 27 | 25 | |
CIMR-AU5A0041UAA | 41 | 40 | 32 | 30 | Flange |
CIMR-AU5A0052UAA | 52 | 50 | 41 | 40 | |
CIMR-AU5A0062UAA | 62 | 60 | 52 | 50 | |
CIMR-AU5A0077UAA | 77 | 75 | 62 | 60 | Flange |
CIMR-AU5A0099UAA | 99 | 100 | 77 | 75 | |
CIMR-AU5A0125UAA | 125 | 125 | 99 | 100 | Flange |
CIMR-AU5A0145UAA | 145 | 150 | 130 | 125 | |
CIMR-AU5A0192UAA | 192 | 200 | 172 | 150 | Flange |
CIMR-AU5A0242UAA | 242 | 250 | 200 | 200 |
- Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
- Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
- Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430. 150 Full-Load Current, Three-Phase Alternating Current Motors
600V, Single-Phase Input, (575V Three-Phase Output)
Drive Model Number 1, 2, 3 | Single Phase Input - Sizing Method A (A) (continuous full power) | Single Phase Input - Sizing Method B (B) (86% max power of connected motor size) | ||||
---|---|---|---|---|---|---|
Without Additional Reactor | With Additional Reactor | |||||
Motor Amps | Motor Size (HP) | Motor Amps | Motor Size (HP) | Motor Amps | Motor Size (HP) | |
CIMR-AU5A0003FAA | 1.7 | 1 | 2.4 | 1.5 | 1.7 | 1 |
CIMR-AU5A0004FAA | 2.4 | 1.5 | 2.7 | 2 | 2.7 | 2 |
CIMR-AU5A0006FAA | 2.7 | 2 | 3.9 | 3 | 3.9 | 3 |
CIMR-AU5A0009FAA | 3.9 | 3 | 6.1 | 5 | 6.1 | 5 |
CIMR-AU5A0011FAA | 2.7 | 2 | 3.9 | 3 | 3.9 | 3 |
CIMR-AU5A0017FAA | 6.1 | 5 | 6.1 | 5 | 9.0 | 7.5 |
CIMR-AU5A0022FAA | 6.1 | 5 | 7.5 | 9.0 | 9.0 | 7.5 |
CIMR-AU5A0027FAA | 9.0 | 7.5 | 11 | 10 | 11.0 | 10 |
CIMR-AU5A0032FAA | 9.0 | 7.5 | 11 | 10 | 11.0 | 10 |
CIMR-AU5A0041FAA | 17 | 15 | 17 | 15 | 22.0 | 20 |
CIMR-AU5A0052FAA | 17 | 15 | 17 | 15 | 22.0 | 20 |
CIMR-AU5A0062FAA | 27 | 25 | 27 | 25 | 32.0 | 30 |
CIMR-AU5A0077FAA | 32 | 30 | 32 | 30 | 41 | 40 |
CIMR-AU5A0099FAA | 32 | 30 | 32 | 30 | 41 | 40 |
CIMR-AU5A0125AAA | 52 | 50 | 52 | 50 | 62 | 60 |
CIMR-AU5A0145AAA | 52 | 50 | 52 | 50 | 62 | 60 |
CIMR-AU5A0192AAA | 77 | 75 | 77 | 75 | 99 | 100 |
CIMR-AU5A0242AAA | 77 | 75 | 77 | 75 | 99 | 100 |
- Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A0081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
- Only models ending in FAA (CIMR-AU2A0211FAA and smaller) come standard with NEMA 1 End Cap Kits. Separately sold kits are available for larger models.
- For Flange Drives, use the sizing method above to determine proper drive size. Use selected model numbers with "UAA" suffix instead of "FAA" or "AAA" suffix.
- Use single phase input sizing method A for applications requiring more than 86% motor power. When sizing with additional reactor, refer to "Reactors for Single Phase Input" section of this price book. Caution: Adding more impedance than specified will degrade performance.
- Use single phase input sizing method B for applications requiring a maximum of 86% motor power.